Installation Guide for Comfort Pack (CPG) Units39IMPORTANT!!!BEFORE REMOVING A WARRANTY COMPRESSOR,PLEASE FILL OUT THE FOLLOWINGAND CALL (800) 523-7138.REMOVAL OF COMPRESSOR WITHOUT FACTORY VERIFICATIONCAN LEAD TO WARRANTY CREDIT BEING DENIED1. Incoming Voltage to Compressor at Contactor is:__________Volts2. Compressor Starting AMP Draw:__________3. Compressor Winding OHM Reading between Terminals C & S:__________4. Compressor Winding OHM Reading between Terminals C & R:__________5. Compressor Winding OHM Reading between Terminals R & S:__________6. Compressor Winding OHM Reading between Terminals C & Ground:__________7. Compressor Winding OHM Reading between Terminals R & Ground:__________8. Compressor Winding OHM Reading between Terminals S & Ground:__________9. Run Capacitor Reading from HERM to COM:__________10. Start Capacitor Reading if Used:__________11. If the Compressor is Operating Please Indicate the Following:Suction Pressure:__________psig Discharge Pressure:___________psigSuper Heat:_____________F Subcooling:______________FACΩΩΩΩΩΩRHERMFANTOP VIEW OF CAPACITORCuF+uF+