8/11k VA 1Phase MBP11Ki 8/11k VA 3PhaseN/A Terminal BlocksOutput(4) C19 + Terminal blocksOverall dimensions D x W x H6.8 x 13.2 x 5.1 in. / 172 x 336 x 130 mmMinimum rack depth for UPS with MBP: 900mm (35.4 inches)Weight (lb / kg)13.7 / 6.2 12.1 / 5.5PerformanceNominal voltage 200 - 240 V ~ 350 - 430 V ~Frequency 50/60 HzInput nominalcurrent50AMaximal power 11000 VAStandards (HotSwap MBP used with UPS)Safety IEC/EN 62040-1 /Ed.1: 2008. UL 17784 th editionIEC/EN 62040-1 / Ed.1: 2008EMC IEC 62040-2 / Ed.2:2005. EN 62040-2 /Ed.2: 2006. FCC part15 Class AIEC 62040-2 / Ed.2: 2005 EN 62040-2 / Ed.2:2006Performance IEC/EN 62040-3 / Ed.2.0: 2011ESD IEC 61000-4-2 : level 3Radiated field IEC 61000-4-3 : level 3EFT IEC 61000-4-4 : level 4Fast transients IEC 61000-4-5 : level 4Electromagnetic field IEC 61000-4-6 : level 3Conducted magneticfieldIEC 61000-4-8 : level 4MarkingcULus Listed / CE CEEnvironmentOperatingtemperature0 to 40°C (32 to 104°F)Storage temperature -15 to 60°C (5 to 140°F)Transit temperature -25 to 55°C (-13 to 130°F)Humidity 0 to 95% no condensingOperation Altitude Up to 3,000 meters (9,843 ft) above sea level with 10% derating per1000mTransit Altitude Up to 10,000 meters (32,808 ft) above sea level66 Installation and User's Guide