Table 15. Weights and dimensions (Power Module) (continued)Model (PowerModule)Dimensions D x W x H (mm /inch) Weight (lb / kg)8K Power Module(KX)700 x 440 x 130 (27.6 x 17.3 x 5.1) 42 / 1911K Power Module(PX)700 x 440 x 130 (27.6 x 17.3 x 5.1) 51 / 2311K Power Module(KX)700 x 440 x 130 (27.6 x 17.3 x 5.1) 46 / 21Minimum rack depth for UPS with MBP: 900mm (35.4 inches)Table 16. Weights and dimensions (EBM)Model (EBM)Dimensions D x W x H (mm /inch) Weight (lb / kg)5594-9BX 680 x 440 x 130 (26.8 x 17.3 x 5.1) 143 / 65Table 17. Environmental and safety standardsEMC certificationsIEC/EN 62040-1: 2008IEC/EN 62040-2: 2006 Cat. C2IEC/EN 62040-3: 2011IEC 60950-1EMC (Emissions) - for outputcable < 10m CISPR22 Class AAS/NZS 22 Class AIEC 61000-3-2 (-3-12)IEC 61000-3-3 (-3-11)EMC (Immunity)IEC 61000-2-2IEC 61000-4-2, Level 3IEC 61000-4-3, Level 3IEC 61000-4-4, Level 4 (also on signal ports)IEC 61000-4-5, Level 4, Criteria BIEC 61000-4-6, Level 3IEC 61000-4-8, Level 4IEC 61000-4-11Agency markings CE / C-TickOperating temperature 0 to 40°C (32 to 104°F) in Online mode, with linearderating for altitudeNote: Thermal protection switches load to Bypass incase of overheating.64 Installation and User's Guide