Separate input source connection (1Phase units)About this task1. Remove the jumper.2. Insert the Normal AC cable through thecable gland.3. Connect the three cables to the NormalAC source terminal blocks.4. Insert the Bypass AC cable through thecable gland.5. Connect the three cables to the BypassAC source terminal blocks.6. Insert the Output cable through the cablegland.7. Connect the three cables to the Outputterminal blocks.8. Put back and secure the terminal blockscover with the screws.9. Tighten the cable glands.Separate input source connection (3Phase units)About this task1. Remove the jumper.2. Insert the Normal AC cable through thecable gland.3. Connect the five cables to the Normal ACsource terminal blocks.4. Insert the Bypass AC cable through thecable gland.5. Connect the three cables to the BypassAC source terminal blocks.6. Insert the Output cable through the cablegland.7. Connect the three cables to the Outputterminal blocks.8. Put back and secure the terminal blockscover with the screws.9. Tighten the cable glands.Frequency converter connection (1Phase units)About this taskImportant: This connection must be carried out by qualified electrical personnel.Before carrying out any connection, check that the upstream protection devices(Normal AC source and Bypass AC source) are open "O" (off).Chapter 4. Power cables connection 29