Table 10. Electrical input connectionsModel Input connection Input cable55594-8PX, 5594-8KX Hardwired Not provided5594-9PX, 5594-9KXTable 11. Electrical outputAll models Normal mode Battery modeVoltage regulation ±1% ±1%Efficiency > 98% (High Efficiency mode)> 94.5% for 8-11kVA models> 91%FrequencyregulationSync with line ±5% of nominal linefrequency (outside this range: ±0.5% ofauto-selected nominal frequency)±0.5% of auto-selectednominal frequencyFrequency 50 or 60Hz, autosensing or configurable as a frequency converterOutput overload100-102% : no alarm102-110% : load transfers to Bypass mode after 2 minutes110-125% : load transfers to Bypass mode after 1 minute125-150% : load transfers to Bypass mode after 10s> 150% : load transfers to Bypass mode after 900msOutput overload(Bypass mode) 100-125% : no alarm125-150% : UPS shuts down after 1 minute> 150% : UPS shuts down after 1sVoltage waveform SinewaveHarmonicdistortion < 2% THDV on linear load< 5% THDV on non-linear loadTransfer time Online mode: 0 ms (no break)High Efficiency mode: 10ms maximum (due to loss of utility power)Power factor 0.9Load crest ratio 3 to 1Table 12. Electrical output connectionsModel Output connection Output cable5594-8PX, 5594-8KX (4) C19 via MBP Not provided5594-9PX, 5594-9KX62 Installation and User's Guide