KM9106 Operators Manual266.5 Inlet TemperatureThe Quintox uses as default the internal ambient sensor when calculating the Nettemperature. If an optional inlet probe is fitted then INLET is used in the calculation.As an alternative to both of the above, the inlet air entering the boiler can be measuredusing the flue probe.NOTE: The probe must not be inserted into the flue until the INLET temperaturehas been set. If resetting the inlet temperature after performing acombustion test ensure the tip of the probe is at the air temperatureTO SET INLET TEMPERATUREWith the flue probe connected to the FLUE temperature connector.Press the -- -- -- -- -- -- -- -- -- -- -- -- --SET-- -- -- -- -- -- -- -- -- -- -- -- --Pressing the key displaysChange to YESSET INLET TEMPNOPosition the tip of the flue probe near theAir inlet of the boiler and when the readingis stable pressPLACE PROBE BYAIR INLET-- -- -- -- -- -- -- -- -- -- -- -- --FLUE . . . 30.0The temperature measured by the flue probe will be set in the Quintox.Press to check the reading.INLETSET/CALENTERINLET