62 FireLite SLC Wiring Manual — P/N 51309:P4 9/17/2014Intelligent Detector Bases and Wireless Gateway Wiring a Sounder Base9.6 Wiring a Sounder BaseFigure 9.4 shows typical wiring of the B200SR or B200SR-LF Sounder Base.9.7 Wiring the W-GATE9.7.1 SLC ConnectionsThe W-GATE Wireless Gateway acts as a bridge between a group of wireless fire devices and aLiteSpeed SLC loop on the MS-9200UDLS. It is powered by the SLC loop or by a regulated,external 24VDC UL-listed power supply. Available wireless devices include a photo detector, aphoto/heat detector, a fixed-temperature heat detector, a rate-of-rise heat detector, and a monitormodule. For details about wireless devices, system setup, and operation, see the SWIFT™ SmartWireless Integrated Fire Technology Instruction Manual.+ -+ -+ -slc-b200srwire.wmfFigure 9.4 Wiring of a B200SR/B200SR-LF Sounder BaseTo next deviceon SLCSLCNote: The “grid” pattern on thesounder base has been removedfor illustration purposes only.UL-Listed24V PowerSupplyOptional SounderInterconnectNOTE: For more detailed wiring on the sounder base, refer to the device’s installation instructions.NOTE: The W-GATE, as part of the wireless network, has been tested for compliance with theFederal Communications Commission (FCC) requirements of the United States Government. Ithas not been evaluated for use outside the USA. Use of this system outside the USA is subject tolocal laws and rules to which this product may not conform. It is the sole responsibility of the userto determine if this product may be legally used outside the USA.NOTE: It is recommended to use the same wire gauge if there are multiple connections to thesame terminal.