40 FireLite SLC Wiring Manual — P/N 51309:P4 9/17/2014Monitor Modules MMF-300-10 Wiring Diagrams5.4.2 Wiring a NFPA Style D IDC with an MMF-300-10Connect the SLC wiring to the module terminals T5 as shown below.Use the rotary switches on the module to set the base SLC address. Each module takes five alternat-ing addresses on the SLC. The remaining module points are automatically assigned to the next fourhigher addresses. (Example: 28, 30, 32, 34 and 36). Refer to “Setting an SLC address for a Multi-Point Module” on page 35.DO NOT set the lowest address above 150 (41 for the MS-9050UD, 90 for the MS-9200, MS-9200UD, and MS-9200UDLS), as the other module points will be assigned to nonexistentaddresses.The figure below shows typical wiring for a supervised and power-limited NFPA Style D (Class A)IDC using an MMF-300-10 module.• Refer to the Device Compatibility Document for compatible smoke detectors.• See “Power Considerations” on page 68 for information on supervising 24 VDC power.24 VDC PowerFiltered, Regulated, Resettable24 VDC Four-wireDetector BaseManual PullStationHeatDetectorIDCOutMMF-300-10SLCIDCReturnSLC-idcD3.cdwmfFigure 5.13 Typical Style D IDC Wiring with an MMF-300-10