FireLite SLC Wiring Manual — P/N 51309:P4 9/17/2014 11Devices Introduction1.4 Devices1.4.1 Isolator ModulesIsolator Modules permit a zone of detectors and modules to be fault isolated from the remainder ofthe SLC loop, allowing critical components to function in the event of a circuit fault. Isolatormodules are required to meet the requirements of an NFPA Style 7 circuit.I300 - Single fault isolator moduleISO-6 - Six fault isolator module1.4.2 Monitor ModulesAddressable modules that allow the control panel to monitor entire circuits of conventional alarminitiating devices, such as manual pull stations, smoke detectors, heat detectors, waterflow andsupervisory devices.MMF-300 - Monitors a Style B (Class B) or Style D (Class A) circuit of dry-contact input devises.MMF-300-10 - Monitors ten (10) Style B (Class B) or five (5) Style D (Class A) normally opencontact device circuits.MMF-301 - Same as the MMF-300 except offered in a smaller package for mounting with Style Bwired devices. This module does not have an LED.MMF-302 - Monitors a single IDC of two-wire smoke detectors.MMF-302-6 - An addressable module that provides an interface between the control panel and six(6) Style B (Class B) or three (3) Style D (Class A) IDCs of two-wire smoke detectors.MDF-300 - Similar to MMF-300, but provides for two independent Style B IDCs.1.4.3 Control ModulesThrough the CMF-300 addressable control module, the control panel can selectively activate aNotification Appliance Circuit (NAC).CMF-300-6 - Similar in operation to the CMF-300, except it can activate six (6) Style Y (Class B)or three (3) Style Z (Class A) NACs.1.4.4 Relay ModulesThe CRF-300 addressable relay module provides the control panel with a dry-contact output foractivating a variety of auxiliary devices.CRF-300-6 - Similar in operation to the CRF-300, except it provides six (6) Form-C relays.1.4.5 Multiple Input/Output ModulesThe CDRM-300 addressable multiple input/output module monitors two (2) Style B input devicesand provides two (2) independent Form-C relay contacts.1.4.6 Intelligent DetectorsAD350 - A multicriteria smoke sensor that combines a photoelectric sensing chamber and 135°F(57.2°C) fixed temperature heat detection. The sensor uses addressable communication to transmitsmoke density and other information to the control panel. It adjusts its detection parameters andalarm threshold depending on the ambient conditions it samples in its environment.AD355 - A multicriteria smoke sensor that combines a photoelectric sensing chamber and 135°F(57.2°C) fixed temperature heat detection. The sensor uses addressable communication to transmitsmoke density and other information to the control panel. It adjusts its detection parameters andalarm threshold depending on the ambient conditions it samples in its environment.