Installation Instructions MB-Secure 1000/2000/3000/4000/5000/6000 213.6 Current consumption of control panel components, detectorsand/or usersThe current values specified are approximate values. The values specified for Active Mode aremaximum values - e.g. with LED displays, relays pulled in. The exact total power consumption must bedetermined by measurement!Device Current consumption at rest / active Number Total currentMB-Secure control panel/basic current See technical specifications 1IB2 Bus extension 65 mAIB2 16 I/O extension See technical dataMB-Secure Siren module(013920) 55 mA / 1.1 AFlash lamp See technical specificationsSirens See technical specificationsBUS-2/BUS-1 IDENTLOC-EU 9 mA / 9 mA / per LED 3 mAIDENTLOC sensor (standard range)(mid. range)(max. range)≤5.5 mA≤10 mA≤15.5 mABUS-2/BUS-1 DUO-I/O module (010120) 5 mA / 45 mABUS-2 16-MG blocking/display module (012542) / per LED 25 mA / 5 mABUS-2 16-MG display module (012548) / per LED 25 mA / 5 mALED keypad (013000) 20 mA / max. 90 mALCD keypad (013001) 20 mA / max. 100 mABUS-2 Comfort Touch Color operating unit (012575.10) 170 mA / 540 mABUS-2 TouchCenter Tuxedo graphical operating unit (013002) 160 mA / max. 310 mABUS-2 TouchCenter Plus graphical operating unit (013003/004/005) 140 mA / max. 260 mABUS-2 motion detector SCM 3000 3 mA / 8 mABUS-2/BUS-1 motion detector Viewguard DUAL AM (033442.20) 4.6 mA / 8.6 mABUS-2/BUS-1 motion detector Viewguard DUAL (033443.20) 4.6 mA / 8.6 mABUS-2/BUS-1 motion detector Viewguard PIR AM (033432.20) 0.6 mA / 4.6 mABUS-2/BUS-1 motion detector Viewguard PIR (033332.20) 0.6 mA / 4.6 mABUS-2/BUS-1 smoke detector base module (062090) 3 mABUS-2 5-input module (013130.10) 6 mA / 46 mABUS-2 5-output module (013131.10) 7 mA / 350 mABUS-2 2-relay 2 detector group module (041220) 5 mA / 45 mABUS-2 Sounder/flasher with 2 inputs (044500) 4 mA / 80 mAIDENT-KEY BUS-2 evaluation unit (023312.17) 15 mA / 45 mA (max.) + peripheralDoor controller module (023350.10) 15 mA / 45 mA (max.) + peripheralIDENT-KEY IK3 operating unit (023320) 15 mA / 50 mAIDENT-KEY IK3 operating unit (023322) 11 mA / 50 mATransmission device DS 7700 (057651.10) 160 mA / 220 mATransmission device DS 6700 (057864) / DS 6750 (057865) 135 mA / 155 mA (without Ethernet)150 mA / 170 mA (with Ethernet)RF BUS-2 wireless receiver (015600) 15 mA