GE Power Management SPM Synchronous Motor Protection & Control4- 114 USER INTERFACE 4.2 KEYPAD INTERFACE44.2.2 CHANGING SETPOINTSTo change SPM setpoints, the user must enter the PROGRAMMING MODE. This can be accomplished withthe motor either off or in running mode. Use the following procedure to enter the PROGRAMMING MODE:1. With the display indicating the following, press the GE key (items in bold italics indicate that they should beblinking on the screen):2. The display should now indicate that the unit is in STAT MODE. Press the GE key.3. Press the GE key. The display should now indicate that the unit is in PROGRAMMING MODE:4. Use the / keys to change the password and then press the key to enter the password.5. The display should now indicate the CONFIGURATIONS menu or the CALIBRATION menu (dependingupon which scroll key was pressed). Use the / keys to select the SETPOINTS menu.6. Press the key to enter the setpoints menu. Once in the SETPOINTS menu, use the / keys tomove through the different setpoints.7. To change a setpoint, press the key as prompted:8. Once the setpoint has been selected, the value of the setpoint should blink. Use the / keys tochange the value of the setpoint and then press the key to continue. If you choose not to change thissetpoint once it has been selected, pressing the GE key deselects the setpoint.9. Additional setpoints can be changed using the above procedure. When all setpoint changes have beenaccomplished, press the GE key. This will return the display to the SETPOINTS main menu. Press the GEkey again and the display will ask to verify that changes should be save. Press to save the setpoints,otherwise press the GE key if you do not want to save the changes.10. Upon pressing (to save the setpoint changes) or the GE key (not wanting to save setpoint changes),the display returns to the PROGRAMMING MODE menu. Press the GE key once to go into TEST MODEand a second time to return to the SPM READY display.Collr-Ring MotorSPM READYSTAT MODESCROLL for menusPROGRAMMING MODESCROLL PASSWORDPASSWORD: 0000ENTER to verifySETPOINTS?ENTER for menusPF TRIP: –0.80SELECT to modifyPF TRIP: –0.80SCROLL to changeSAVE CHANGES?ENTER to save ...ENTERENTERENTERENTERENTERENTER