GE Multilin F60 Feeder Protection System 6-216 ACTUAL VALUES 6.3 METERING6Voltage harmonics are not available on F60 relays configured with the high-impedance fault detection (Hi-Z) fea-ture.Voltage harmonics are calculated only for Wye connected phase VTs. Ensure the SYSTEM SETUP Ö AC INPUTS ÖØVOLTAGE BANK F5 ÖØ PHASE VT XX CONNECTION setting is “Wye” to enable voltage harmonics metering.6.3.3 SENSITIVE DIRECTIONAL POWERPATH: ACTUAL VALUES ÖØ METERING ÖØ SENSITIVE DIRECTIONAL POWERThe effective operating quantities of the sensitive directional power elements are displayed here. The display may be usefulto calibrate the feature by compensating the angular errors of the CTs and VTs with the use of the RCA and CALIBRATIONsettings.6.3.4 SYNCHROCHECKPATH: ACTUAL VALUES ÖØ METERING ÖØ SYNCHROCHECK Ö SYNCHROCHECK 1(2)The actual values menu for synchrocheck 2 is identical to that of synchrocheck 1. If a synchrocheck function setting is "Dis-abled", the corresponding actual values menu item will not be displayed.6.3.5 TRACKING FREQUENCYPATH: ACTUAL VALUES ÖØ METERING ÖØ TRACKING FREQUENCYThe tracking frequency is displayed here. The frequency is tracked based on the selection of the reference source with theFREQUENCY AND PHASE REFERENCE setting in the SETTINGS ÖØ SYSTEM SETUP ÖØ POWER SYSTEM menu. Refer to thePower System section of chapter 5 for additional details. SENSITIVE DIRECTIONAL POWERDIRECTIONAL POWER 13Φ: 0.000 WMESSAGE DIRECTIONAL POWER 23Φ: 0.000 W SYNCHROCHECK 1SYNCHROCHECK 1 DELTAVOLT: 0.000 VMESSAGE SYNCHROCHECK 1 DELTAPHASE: 0.0°MESSAGE SYNCHROCHECK 1 DELTAFREQ: 0.00 Hz TRACKING FREQUENCYTRACKING FREQUENCY:60.00 HzNOTENOTE