5-184 F60 Feeder Protection System GE Multilin5.6 CONTROL ELEMENTS 5 SETTINGS55.6.11 MONITORING ELEMENTSa) MAIN MENUPATH: SETTINGS ÖØ CONTROL ELEMENTS ÖØ MONITORING ELEMENTSb) HIGH IMPEDANCE FAULT DETECTIONPATH: SETTINGS ÖØ CONTROL ELEMENTS ÖØ MONITORING ELEMENTS Ö HI-Z MONITORING ELEMENTS HI-Z See page 5–184.MESSAGE BREAKER 1 ARCING CURRENT See page 5–190.MESSAGE BREAKER 2 ARCING CURRENT See page 5–190.MESSAGE BREAKER FLASHOVER 1 See page 5–192.MESSAGE BREAKER FLASHOVER 2 See page 5–192.MESSAGE BREAKER RESTRIKE 1 See page 5–196.MESSAGE INCIPIENT FAULT 1 See page 5–198.MESSAGE INCIPIENT FAULT 2 See page 5–198.MESSAGE VT FUSE FAILURE 1 See page 5–200.MESSAGE VT FUSE FAILURE 2 See page 5–200. HI-ZHI-Z FUNCTION:DisabledRange: Disabled, EnabledMESSAGE HI-Z SOURCE:SRC 1Range: SRC 1, SRC 2MESSAGE HI-Z ARCINGSENSITIVITY: 5Range: 1 to 10 in steps of 1MESSAGE HI-Z ARCING DET SOERESET TIME: 0.0 sRange: 0.0 to 6000.0 s in steps of 0.1MESSAGE HI-Z PHASE EVENTCOUNT: 30Range: 10 to 250 in steps of 1MESSAGE HI-Z GROUND EVENTCOUNT: 30Range: 10 to 500 in steps of 1MESSAGE HI-Z EVENT COUNTTIME: 15 minRange: 5 to 180 min. in steps of 1MESSAGE HI-Z OC PROTECTIONCOORD TIMEOUT: 15 sRange: 10 to 200 s in steps of 1MESSAGE HI-Z PHASE OC MINPICKUP: 1.50 puRange: 0.01 to 10.00 pu in steps of 0.01