6-30 F60 Feeder Protection System GE Multilin6.4 RECORDS 6 ACTUAL VALUES66.4.5 PHASOR MEASUREMENT UNIT RECORDSPATH: ACTUAL VALUES RECORDS PMU RECORDSThe number of triggers applicable to the phasor measurement unit recorder is indicated by the NUMBER OF TRIGGERS value.The status of the phasor measurement unit recorder is indicated as follows:PATH: ACTUAL VALUES RECORDS PMU RECORDS PMU 1 RECORDING6.4.6 BREAKER MAINTENANCEPATH: ACTUAL VALUES RECORDS MAINTENANCE BREAKER 1(2)There is an identical menu for each of the breakers. The BKR 1 ARCING AMP values are in units of kA 2 -cycles. Refer to theCOMMANDS CLEAR RECORDS menu for clearing breaker arcing current records. The BREAKER OPERATING TIME isdefined as the slowest operating time of breaker poles that were initiated to open. PMU RECORDSNUMBER OF TRIGGERS:0Range: 0 to 65535 in steps of 1MESSAGE PMU 1 RECORDING See below. PMU 1 RECORDINGPMU 1 FORCE TRIGGER:YesRange: No, YesMESSAGE PUM 1 AVAILABLERECORDS: 0Range: 0 to 65535 in steps of 1MESSAGE PUM 1 SECONDSPER RECORD: 0.0Range: 0 to 6553.5 in steps of 0.1MESSAGE PUM 1 LAST CLEARED:2013/07/14 15:40:16Range: date and time in format shown BREAKER 1BKR 1 ARCING AMP φA:0.00 kA2-cycMESSAGE BKR 1 ARCING AMP φB:0.00 kA2-cycMESSAGE BKR 1 ARCING AMP φC:0.00 kA2-cycMESSAGE BKR 1 OPERATING TIMEφA: 0 msMESSAGE BKR 1 OPERATING TIMEφB: 0 msMESSAGE BKR 1 OPERATING TIMEφC: 0 msMESSAGE BKR 1 OPERATINGTIME: 0 ms