GE Multilin F60 Feeder Protection System 5-1035 SETTINGS 5.4 SYSTEM SETUP5b) VOLTAGE BANKSPATH: SETTINGS SYSTEM SETUP AC INPUTS VOLTAGE BANK F5Because energy parameters are accumulated, these values should be recorded and then resetimmediately prior to changing VT characteristics.One bank of phase/auxiliary VTs can be set, where voltage banks are denoted in the following format (X represents themodule slot position letter):Xa, where X = {F} and a = {5}.See the Introduction to AC Sources section at the beginning of this chapter for additional details.With VTs installed, the relay can perform voltage measurements as well as power calculations. Enter the PHASE VT F5 CON-NECTION made to the system as “Wye” or “Delta”. An open-delta source VT connection would be entered as “Delta”.The nominal PHASE VT F5 SECONDARY voltage setting is the voltage across the relay input terminals when nominalvoltage is applied to the VT primary.For example, on a system with a 13.8 kV nominal primary voltage and with a 14400:120 volt VT in a delta connec-tion, the secondary voltage would be 115; that is, (13800 / 14400) × 120. For a wye connection, the voltage valueentered must be the phase to neutral voltage which would be 115 / = 66.4.On a 14.4 kV system with a delta connection and a VT primary to secondary turns ratio of 14400:120, the voltagevalue entered would be 120; that is, 14400 / 120.If the PHASE VT F5 CONNECTION is set to “Delta”, the relay will not calculate voltage harmonics.5.4.2 POWER SYSTEMPATH: SETTINGS SYSTEM SETUP POWER SYSTEM VOLTAGE BANK F5PHASE VT F5CONNECTION: WyeRange: Wye, DeltaMESSAGE PHASE VT F5SECONDARY: 66.4 VRange: 25.0 to 240.0 V in steps of 0.1MESSAGE PHASE VT F5RATIO: 1.00 :1Range: 1.00 to 24000.00 in steps of 0.01MESSAGE AUXILIARY VT F5CONNECTION: VagRange: Vn, Vag, Vbg, Vcg, Vab, Vbc, VcaMESSAGE AUXILIARY VT F5SECONDARY: 66.4 VRange: 25.0 to 240.0 V in steps of 0.1MESSAGE AUXILIARY VT F5RATIO: 1.00 :1Range: 1.00 to 24000.00 in steps of 0.01 POWER SYSTEMNOMINAL FREQUENCY:60 HzRange: 25 to 60 Hz in steps of 1MESSAGE PHASE ROTATION:ABCRange: ABC, ACBMESSAGE FREQUENCY AND PHASEREFERENCE: SRC 1Range: SRC 1, SRC 2, SRC 3, SRC 4MESSAGE FREQUENCY TRACKING:EnabledRange: Disabled, EnabledNOTICENOTE3NOTE