2-14 F60 Feeder Protection System GE Multilin2.2 SPECIFICATIONS 2 PRODUCT DESCRIPTION2HI-ZDetections: Arc Suspected, Arc Detected, DownedConductor, Phase IdentificationPHASOR MEASUREMENT UNITOutput format: per IEEE C37.118 standardNumber of channels: 14 synchrophasors, 8 analogs, 16 digi-talsTVE (total vector error) <1%Triggering: frequency, voltage, current, power, rateof change of frequency, user-definedReporting rate: 1, 2, 5, 10, 12, 15, 20, 25, 30, 50, or 60times per secondNumber of clients: One over TCP/IP port, two over UDP/IPportsAC ranges: As indicated in appropriate specificationssectionsNetwork reporting format: 16-bit integer or 32-bit IEEE floatingpoint numbersNetwork reporting style: rectangular (real and imaginary) or polar(magnitude and angle) coordinatesPost-filtering: none, 3-point, 5-point, 7-pointCalibration: ±5°2.2.4 METERINGRMS CURRENT: PHASE, NEUTRAL, AND GROUNDAccuracy at0.1 to 2.0 × CT rating: ±0.25% of reading or ±0.1% of rated(whichever is greater)> 2.0 × CT rating: ±1.0% of readingRMS VOLTAGEAccuracy: ±0.5% of reading from 10 to 208 VREAL POWER (WATTS)Accuracy: ±1.0% of reading at–0.8 < PF ≤ –1.0 and 0.8 < PF ≤ 1.0REACTIVE POWER (VARS)Accuracy: ±1.0% of reading at –0.2 ≤ PF ≤ 0.2APPARENT POWER (VA)Accuracy: ±1.0% of readingWATT-HOURS (POSITIVE AND NEGATIVE)Accuracy: ±2.0% of readingRange: ±0 to 1 × 10 6 MWhParameters: three-phase onlyUpdate rate: 50 msVAR-HOURS (POSITIVE AND NEGATIVE)Accuracy: ±2.0% of readingRange: ±0 to 1 × 10 6 MvarhParameters: three-phase onlyUpdate rate: 50 msCURRENT HARMONICSHarmonics: 2nd to 25th harmonic: per phase, dis-played as a % of f1 ( fundamental fre-quency phasor)THD: per phase, displayed as a % of f 1Accuracy:HARMONICS: 1. f1 > 0.4pu: (0.20% + 0.035% / harmonic) ofreading or 0.15% of 100%, whichever isgreater2. f1 < 0.4pu: as above plus %error of f 1THD: 1. f1 > 0.4pu: (0.25% + 0.035% / harmonic) ofreading or 0.20% of 100%, whichever isgreater2. f1 < 0.4pu: as above plus %error of f 1VOLTAGE HARMONICSHarmonics: 2nd to 25th harmonic: per phase, dis-played as a % of f1 ( fundamental fre-quency phasor)THD: per phase, displayed as a % of f 1Accuracy:HARMONICS: 1. f1 > 0.4pu: (0.20% + 0.035% / harmonic) ofreading or 0.15% of 100%, whichever isgreater2. f1 < 0.4pu: as above plus %error of f 1THD: 1. f1 > 0.4pu: (0.25% + 0.035% / harmonic) ofreading or 0.20% of 100%, whichever isgreater2. f1 < 0.4pu: as above plus %error of f 1FREQUENCYAccuracy atV = 0.8 to 1.2 pu: ±0.01 Hz (when voltage signal is usedfor frequency measurement)I = 0.1 to 0.25 pu: ±0.05 HzI > 0.25 pu: ±0.02 Hz (when current signal is used forfrequency measurement)