6-24 F60 Feeder Protection System GE Multilin6.3 METERING 6 ACTUAL VALUES6The above actual values are displayed without the corresponding time stamp as they become available per the recordingrate setting. Also, the recording post-filtering setting is applied to these values.6.3.11 TRANSDUCER INPUTS AND OUTPUTSPATH: ACTUAL VALUES METERING TRANSDUCER I/O DCMA INPUTS DCMA INPUT xxActual values for each DCmA input channel that is enabled are displayed with the top line as the programmed channel IDand the bottom line as the value followed by the programmed units.PATH: ACTUAL VALUES METERING TRANSDUCER I/O RTD INPUTS RTD INPUT xxActual values for each RTD input channel that is enabled are displayed with the top line as the programmed channel ID andthe bottom line as the value.MESSAGE PMU 1 V0:0.0000 kV, 0.00°Range: Substituted with zero if delta-connected VTs.MESSAGE PMU 1 IA:0.0000 kA, 0.00°MESSAGE PMU 1 IB:0.0000 kA, 0.00°MESSAGE PMU 1 IC:0.0000 kA, 0.00°MESSAGE PMU 1 IG:0.0000 kA, 0.00°MESSAGE PMU 1 I1:0.0000 kA, 0.00°MESSAGE PMU 1 I2:0.0000 kA, 0.00°MESSAGE PMU 1 I0:0.0000 kA, 0.00°MESSAGE PMU 1 FREQUENCY:0.0000 HzMESSAGE PMU 1 df/dt:0.0000 Hz/sMESSAGE PMU 1 CONFIG CHANGECOUNTER: 0Range: 0 to 65535 DCMA INPUT xxDCMA INPUT xx0.000 mA RTD INPUT xxRTD INPUT xx-50 °C