CHAPTER 6: ACTUAL VALUES PRODUCT INFORMATIONF60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 6-316There is an identical menu for each of the breakers.The BKR 1 ACC ARCING AMP values are in units of kA2 -cycles. See the COMMANDS CLEAR RECORDS menu for clearingbreaker arcing current records.The BREAKER OPERATING TIME is defined as the slowest operating time of breaker poles that were initiated to open.All of the values are stored in non-volatile memory and retained with power cycling.6.5.7 Hi-Z recordsACTUAL VALUES RECORDS HIZ RECORDSTwo types of high impedance fault detection element records are stored in non-volatile memory and available from thismenu. If the element is triggered by a high impedance overcurrent condition, then the records display in the RMS 1 to RMS4 actual values. If the element is triggered by high impedance fault detection arcing algorithm, then the records display inthe HIZ 1 to HIZ 4 actual values. See the High-Impedance Fault Detection (Hi-Z) section near the end of chapter 5 forinformation.6.6 Product information6.6.1 Model informationACTUAL VALUES PRODUCT INFO MODEL INFORMATION HIZ RECORDS FORCE TRIGGER:No HIZ 1:NONE1970/01/01 00:00:00 HIZ 2:NONE1970/01/01 00:00:00 HIZ 3:NONE1970/01/01 00:00:00 HIZ 4:NONE1970/01/01 00:00:00 RMS 1:NONE1970/01/01 00:00:00 RMS 2:NONE1970/01/01 00:00:00 RMS 3:NONE1970/01/01 00:00:00 RMS 4:NONE1970/01/01 00:00:00 MODEL INFORMATION ORDER CODE LINE 1:F60-A00-AAA-A0A-A0A-Range: standard GE order code format ORDER CODE LINE 2:A0A-A0A-A0ARange: up to 20 alphanumeric characters ORDER CODE LINE 3: Range: up to 20 alphanumeric characters ORDER CODE LINE 4: Range: up to 20 alphanumeric characters