5-40 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUALPRODUCT SETUP CHAPTER 5: SETTINGS5Figure 5-12: Configurable navigation editorTo use the feature, select a CONDITION, select an ACTIVATE PAGE, then save.CONDITIONRange: OFF, ON, any FlexLogic operandDefault: OFFSelect the FlexLogic operand for the trigger. When it transitions from Off to On, it opens the page specified by theACTIVATE PAGE setting. The FlexLogic operands selectable depend on product. Select it from the drop-down list. Or clickor select the field and start typing to auto-fill. For example, typing F displays FIRST ETHERNET FAIL, while typing BRdisplays the first breaker option.ACTIVATE PAGERange: Product Information, SLD 1…5, Annunciator, Annunciator 1…8, Actual Values Phasors 1…6, Tabular 1…5, EventRecords, TargetsDefault: Product InformationThis setting specifies the page to display on the graphical front panel when the FlexLogic operand selected by itsCONDITON setting transitions from Off to On.The "Annunciator" option without a page number specifies the first annunciator page in the following sequence:– The first annunciator page that contains an annunciator window that is in alarm (fast flash)– The first annunciator page that contains an annunciator window that is in ringback. Ringback is a "return alert."Visual and audible signals are given when conditions return to normal, then the sequence returns to normal bypushing the RESET button.– The first annunciator page that contains an annunciator window that is in abnormal state– Annunciator page 1The Tabular option displays a configured actual values/metering page.The Targets option displays error messages.5.3.4 Clear relay recordsSETTINGS PRODUCT SETUP CLEAR RELAY RECORDS CLEAR RELAY RECORDS CLEAR FAULT REPORTS:OffRange: FlexLogic operand CLEAR EVENT RECORDS:OffRange: FlexLogic operand CLEAR OSCILLOGRAPHY:OffRange: FlexLogic operand