CHAPTER 5: SETTINGS TRANSDUCER INPUTS/OUTPUTSF60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-3515on both channels (teleprotection outputs at the sending end or corresponding teleprotection inputs at the receiving end).On three-terminal two-channel systems, redundancy is achieved by programming signal re-transmittal in the case ofchannel failure between any pair of relays.Figure 5-196: Teleprotection input/output processing5.11 Transducer inputs/outputs5.11.1 DCmA inputsSETTINGS TRANSDUCER I/O DCMA INPUTS DCMA INPUT H1(W8) DCMA INPUT H1 DCMA INPUT H1FUNCTION: DisabledRange: Disabled, Enabled DCMA INPUT H1 ID:DCMA Ip 1Range: up to 20 alphanumeric characters DCMA INPUT H1UNITS: μARange: six alphanumeric characters DCMA INPUT H1RANGE: 0 to -1 mARange: 0 to –1 mA, 0 to +1 mA, –1 to +1 mA, 0 to 5mA, 0 to 10mA, 0 to 20 mA, 4 to 20 m DCMA INPUT H1 MINVALUE: 0.000Range: –9999.999 to +9999.999 in steps of 0.001 DCMA INPUT H1 MAXVALUE: 0.000Range: –9999.999 to +9999.999 in steps of 0.001The F60 is provided with optional DCmA capability. This feature is specified as an option at the time ofordering. See the Order Codes section in chapter 2 for details.