CHAPTER 5: SETTINGS GROUPED ELEMENTSF60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-1935Each of the six setting group menus is identical. Setting group 1 (the default active group) is active automatically when noother group is active.If the device incorrectly switches to group 1 after power cycling, upgrade the firmware to version 7.31 or later to correctthis issue.5.7.3 Load encroachmentSETTINGS GROUPED ELEMENTS SETTING GROUP 1(6) LOAD ENCROACHMENTThe load encroachment element responds to the positive-sequence voltage and current and applies a characteristic asshown in the figure. WATTMETRIC GROUND FAULTSee page 5-215 GROUND CURRENTSee page 5-219 NEGATIVE SEQUENCE CURRENTSee page 5-226 BREAKER FAILURESee page 5-232 VOLTAGE ELEMENTSSee page 5-241 POWERSee page 5-248 LOAD ENCROACHMENT LOAD ENCROACHMENTFUNCTION: DisabledRange: Disabled, Enabled LOAD ENCROACHMENTSOURCE: SRC 1Range: SRC 1, SRC 2, SRC 3, SRC 4 LOAD ENCROACHMENTMIN VOLT: 0.250 puRange: 0.004 to 3.000 pu in steps of 0.001 LOAD ENCROACHMENTREACH: 1.00 ΩRange: 0.02 to 250.00 ohms in steps of 0.01 LOAD ENCROACHMENTANGLE: 30°Range: 5 to 50° in steps of 1 LOAD ENCROACHMENTPKP DELAY: 0.000 sRange: 0.000 to 65.535 s in steps of 0.001 LOAD ENCROACHMENTRST DELAY: 0.000 sRange: 0.000 to 65.535 s in steps of 0.001 LOAD ENCRMNT BLK:OffRange: Flexlogic operand LOAD ENCROACHMENTTARGET: Self-resetRange: Self-reset, Latched, Disabled LOAD ENCROACHMENTEVENTS: DisabledRange: Disabled, Enabled