Installation Methods• Perform one of the following rack installation methods to ensure the safe use of an ETERNUS AF that is instal-led in a rack:- To secure a rack, use a rack without stabilizers and secure it to the building with the leveling feet.- If a rack is not to be secured, make sure to use a rack with stabilizers and use these stabilizers to prevent therack from toppling over.• Which installation method should be used depends on the installation location, the floor conditions, and thetype of racks that are to be used. Contact your installation contractor for more details regarding installationand how the installation should actually be performed.Load Bearing Capacity for FloorsMake sure that the following relationship between the load bearing capacity of the floor and the weight of theETERNUS AF is maintained.(Load bearing capacity of the floor) > (ETERNUS AF weight ¸ Installation area that includes service areas)If the condition above is not satisfied, additional measures are required to ensure sufficient load bearing capaci-ty.Contact your installation contractor for details about the necessary measures that must be taken.Outlet/Socket SpecificationsThis section explains the power connection specifications of the ETERNUS AF storage systems.■ Power Supply UnitsPower can be supplied from two power sources in the ETERNUS AF because each enclosure has two power supplyunits.During normal operation, each of the power sources supplies half of the necessary power.When one of the power supply lines fails, all of the necessary power is supplied from only one power source.Using the same power supply condition for all of the power supply units is recommended so that different powersupply conditions (input voltage) are not used for the ETERNUS AF.■ Current ConsumptionThe following table shows the current consumption (guideline) of each power cord that is used for the connec-tions to each type of enclosure.Table 5 Current Consumption of Each Power CordComponent name VoltageAC100V AC200VController enclosure 8.2A 4.1ADrive enclosure 4.4A 2.2AWhen using power distribution units, make sure that the current capacity totaling the current consumption val-ue of power cords that connect to the enclosures does not exceed the actual usage rating of the power distribu-tion unit.1. ETERNUS AF InstallationOutlet/Socket Specifications17FUJITSU Storage ETERNUS AF250 S2, ETERNUS AF250 All-Flash Arrays Site Planning GuideCopyright 2021 FUJITSU LIMITEDP3AG-1812-06ENZ0