N-Tron 1000 Series Hardware Guide 1-9Introduction and Specifications Revised 2015-03-24Model 1008TX - Key SpecificationsTable 7. 1008TX Key SpecificationsModel 1008TX Regulatory ApprovalsSafetyFor use in Class I, Division 2, Groups A, B, C and D Hazardous Locations.• UL 508, Industrial Control Equipment.• ANSI/ISA-12.12.01-2013 for use in Class I and II, Division 2 and Class III Divisions 1 and 2 Hazardous (Classi-fied) Locations Groups A, B, C, D. T4.• cUL C22.2 No. 14-M05• cUL C22.2 No. 213-M1987 for use in Class I, Division 2 Hazardous Locations.EMI• FCC Title 47, Part 15, Subpart B - Class A• Industry Canada ICES-003 – Class A• EN 55011 - Class A• EN 61000-6-4• EN 61000-3-2/3PHYSICAL ELECTRICALHeight 4.63” (11.76 cm) Input Voltage 10-49 VDC (Regulated)Width 1.55” (3.94 cm) Input Current 290mA max. @ 24VDC(Steady State)Depth w/ typicalSFP installed4.08” (10.37 cm) Inrush Current 20 Amp/0.06 ms max. @24VDCWeight 0.7 lbs (0.32 kg) Input Ripple Less than 100 mVDIN Rail 35 mm Input Wire Size 12-24 AWGENVIRONMENTAL NETWORK MEDIAOperating Temperature -40°C to 85°C 10BaseT Cat-3Storage Temperature -40°C to 85°C 100BaseT Cat-5Operating Humidity 10% to 90%(Non Condens-ing)1000BaseT Cat-5eOperating Altitude 0 to 10,000 ft.CONNECTORS RECOMMENDED MINIMUM WIRING CLEARANCE10/100/1000BaseTX Eight (8) RJ45 TX CopperPortsTop 1 " (2.54 cm)Front 2 " (5.08 cm)Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com