14Sensor error detection limitserror indicationsSensor error detection (SE.BR, SE.SH):Input Range Readout LimitCURR Loop break (4..20 mA) SE.BR <= 3.6 mA; > = 21 mAPOTM All, SE.BR on all 3wire SE.BR > ca. 126 kΩLIN.R 0...800 Ω SE.BR > ca. 875 Ω0...10 kΩ SE.BR > ca. 11 kΩTEMPTC SE.BR > ca. 750 kΩ / (1.25 V)RTD, 2, 3, and 4wireNo SE.SH for Pt10, Pt20 and Pt50SE.BR > ca. 15 kΩSE.SH < ca. 15 ΩDisplay readout below min. / above max. (1999, 9999):Input Range Readout LimitAll All 1999 Display readout <19999999 Display readout >9999Readout at hardware errorError search Readout Error causeTest of internal CJC sensor CJ.ER CJC sensor defect or temperature outside rangeChecksum test of the setup in FLASH FL.ER Error in FLASHCheck measurement of analogue output current AO.ER 1) Incorrect current output(only S4...20/S20...4 mA)Communications test PGMMOD00 / device NO.CO Connection errorCheck that input signal matches input setup IN.ER 1) Error levels on inputCheck that saved setup in PGMMOD00 matches device TY.ER Setup mismatch! Error indications in the display flash once per second. The help text explains the error.1) The error is reset by switching off and then switching on the supply voltage to the device.