Setting 0: Auto detectionSetting 1: 10 kbpsSetting 2: 20 kbpsSetting 3: 50 kbpsSetting 4: 125 kbpsSetting 5: 250 kbpsSetting 6: 500 kbpsSetting 7: 800 kbpsSetting 8: 1 Mbpsu BACnet ParametersParameters F6-45 to F6-49 set the drive to operate on a BACnet network.n F6-45: BACnet Node AddressSets the node address for a BACnet option card.No. Parameter Name Setting Range DefaultF6-45 BACnet Node Address 0 to 127 1n F6-46: BACnet Baud RateSets the node address for a BACnet option card.No. Parameter Name Setting Range DefaultF6-46 BACnet Baud Rate 0 to 8 3Setting 0: 1200Setting 1: 2400Setting 2: 4800Setting 3: 9600Setting 4: 19200Setting 5: 38400Setting 6: 57600Setting 7: 76800Setting 8: 115200n F6-47: Rx to Tx Wait TimeSets the wait time between receiving and sending for BACnet.No. Parameter Name Setting Range DefaultF6-47 Rx to Tx Wait Time 5 to 65 ms 5 msn F6-48: BACnet Device Object Identifier 0Sets the least significant word for BACnet.No. Parameter Name Setting Range DefaultF6-48 BACnet Device Object Identifier 0 0 to FFFF 0n F6-49: BACnet Device Object Identifier 1Sets the least significant word for BACnet.No. Parameter Name Setting Range DefaultF6-49 BACnet Device Object Identifier 1 0 to 3F 0u DeviceNet ParametersParameters F6-50 through F6-63 set the drive to operate on a DeviceNet network.1.6 F: Option Settings74 YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual