u Drive Cooling Fan Replacement: Models 2o0028 to 2o0130 and 4o0011 to 4o0124WARNING! Electrical Shock Hazard. Do not connect or disconnect wiring while the power is on. Failure to comply can result in seriouspersonal injury. Before servicing the drive, disconnect all power to the equipment. The capacitor for the control power supply remains chargedeven after the power supply is turned off. After shutting off the power, wait for at least the amount of time specified on the drive beforetouching any components.CAUTION! Burn Hazard. Do not touch a hot drive heatsink. Failure to comply could result in minor or moderate injury. Shut off the powerto the drive when replacing the cooling fan. To prevent burns, wait at least 15 minutes and ensure the heatsink has cooled down.NOTICE: Prevent Equipment Damage. Follow cooling fan and circulation fan replacement instructions. Improper fan replacement couldcause damage to equipment. Make sure the fan is facing upwards when installing the replacement fan into the drive. Replace all fans whenperforming maintenance to help ensure maximum useful product life.n Removing the Cooling Fan Guard and Cooling Fan1. Depress the right and left sides of the fan guard tabs and pull upward. Remove the fan guard from the top of the drive.Figure 2.5 Remove the Fan Guard2. Remove the cooling fan cartridge.Figure 2.6 Remove the Cooling Fan Cartridge3. Disconnect the pluggable connector and remove the fan.Figure 2.7 Disconnect the Cooling Fan2.5 Drive Cooling Fans176 YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual