No.(Addr.Hex) Name LCD Display Description Values Pageo2-19(061F) Selection of ParameterWrite during UvParameterSet Sel0: Disabled1: EnabledDetermines whether parameter settings can be changed duringa control circuit undervoltage condition. To be used with 24 VPower Supply Unit Built-in model.0: Disabled1: EnabledDefault: 0Range: 0, 1 137u o3: Copy FunctionNo.(Addr.Hex) Name LCD Display Description Values Pageo3-01(0515) Copy Function SelectionCOPY SELECT0: COPY SELECT1: INV→OP READ2: OP→INV WRITE3: OP←→INVVERIFY0: No action1: Read parameters from the drive, saving them onto the HOAkeypad.2: Copy parameters from the digital operator, writing them to thedrive.3: Verify parameter settings on the drive to check if they matchthe data saved on the HOA keypad.Default: 0Range: 0 to 3 138o3-02(0516) Copy Allowed Selection Read Allowable0: Disabled1: Enabled0: Read operation prohibited1: Read operation allowed Default: 0Range: 0, 1 138u o4: Maintenance Monitor SettingsNo.(Addr.Hex) Name LCD Display Description Values Pageo4-01(050B) Cumulative OperationTime Setting DrvElapsTimeCnt Sets the value for the cumulative operation time of the drive inunits of 10 h. Default: 0 hMin.: 0Max.: 9999 138o4-02(050C) Cumulative OperationTime SelectionElapsTimeCntSet0: Power-On Time1: Running Time0: Logs power-on time1: Logs operation time when the drive output is active (outputoperation time).Default: 1Range: 0, 1 138o4-03(050E) Cooling Fan OperationTime Setting FanElapsTimeCn Sets the value of the fan operation time monitor U4-03 in unitsof 10 h. Default: 0 hMin.: 0Max.: 9999 138o4-05(051D) Capacitor MaintenanceSetting BusCap Maint Set Sets the value of the Maintenance Monitor for the capacitors. SeeU4-05 to check when the capacitors may need to be replaced. Default: 0%Min.: 0Max.: 150 139o4-07(0523)DC Bus Pre-ChargeRelay MaintenanceSetting ChrgCircMaintSet Sets the value of the Maintenance Monitor for the soft chargebypass relay. See U4-06 to check when the bypass relay may needto be replaced.Default: 0%Min.: 0Max.: 150 139o4-11(0510) U2, U3 Initialization Fault Data Init0: No Reset1: Reset0: U2-oo and U3-oo monitor data is not reset when the driveis initialized (A1-03).1: U2-oo and U3-oo monitor data is reset when the drive isinitialized (A1-03).Default: 0Range: 0, 1 139o4-12(0512) kWh MonitorInitializationkWh Monitor Init0: No Reset1: Reset0: U4-10 and U4-11 monitor data is not reset when the drive isinitialized (A1-03).1: U4-10 and U4-11 monitor data is reset when the drive isinitialized (A1-03).Default: 0Range: 0, 1 139o4-13(0528)Number of RunCommands CounterInitializationRun Counter Init0: No Reset1: Reset0: Number of Run commands counter is not reset when the driveis initialized (A1-03).1: Number of Run commands counter is reset when the drive isinitialized (A1-03).Default: 0Range: 0, 1 139o4-17(3100) Set/Reset Real TimeClockSet Time0: — —1: Set2: ResetSets the current date and time for the Real Time Clock.0: — — No Setting1: Real Time Clock Set2: Real Time Clock ResetDefault: 0Range: 0 to 2 139o4-19(113A) Power Unit Price Energy Price/kWh Sets the price per 1 kWh to calculate the power rate displayed fortotal consumed power (U9-07 to U9-10) and total regeneratedpower (U9-11 to U9-14).Default: 000.00Min.: 000.00Max.: 650.00 140A.12 o: Operator-Related Settings238 YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual