9465/9465KPM System Manual3-24location of incoming line devices keeps power wire runs as short as possible andminimizes electrical noise transmitted to the 9465.• Make sure the location does not exceed the 9465/9465KPM’s shock, vibration, andtemperature specifications.• Install in the panel in such a way as to ensure that it does not cause a hazard fromuneven mechanical loading.• Avoid overloading the supply circuitEnclosuresThe systems are designed for installation within a clean and dry enclosure for both ordi-nary and hazardous locations. The front panel meets the requirements for Type 4, 4X,and 12 enclosures. The enclosure used for Class I hazardous locations should have aminimum rating of Type 12 (NEMA 12, IP 5X). However, Type 4 (IP 6X) enclosures arestrongly recommended.WarningThe floppy disk/keyboard port access door must be closed and latched atall times to maintain a proper seal against water and dust.Panel flatness and rigidity are important to maintain a proper panel seal. If you are usingnon-metal type enclosures, such as plastic or fiberglass, install a rigid metal stiffener be-hind the front panel. Failure to do so may result in an inadequate panel seal due to flex-ure of the front panel material between the stud mounts. Tighten the nuts on the mount-ing studs to 25-inch pounds.The requirements for enclosure fittings, conduit, and wiring vary according to the spe-cific rating of the location and the type of flammable or combustible material involved.Those requirements are beyond the scope of this document and it is the responsibility ofthe customer to ensure that their installation is compliant with codes and regulations thatapply to their specific location. Reference NFPA 70, Article 500 for specific regulationsin the United States.System PowerOn the average, the temperature within the system is 7-10°C higher than that outside theenclosure. When the ambient (exterior) temperature reaches 42°C, the system’s powersupply will begin to derate at a rate of 3.25 watts per increase of 1°C.The 9465/9465KPM is rated to work at temperatures up to 50°C (at 50ºC, no more than100 watts of expansion can be added to the system).Refer to the table below for more information.Voltage Available Current aAHIP5+ AHIP6++3.3 VDC 0A 10.6Ab+5 VDC 12.48A 10.6AbArtisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com