AC100 HIGH-PERFORMANCE VC INVERTER MANUAL FUNCTION PARAMETER SPECIFICATION143T 3 T 4 T 5T 2 T 1 T 4 T 3T 1: A C C by A C C tim eT 2: preset frequency lasting tim eT 3: sw ing frequency rising tim eT 4: sw ing frequency falling tim eS w in g fre que ncy chartO NT 1S w in g fre quencyra nge ( F C .52 )S tart-up fre quencyran ge ( F C .53 )O utput frequencyT 5: D E C by D E C tim etim eLow er sw ing frequencyC entral sw ing frequencyU pper sw ing frequency(F C .50)S w ing frequency am plitudeR unning com m and8.13 Communication Control Function ParametersFd.00 Main-slave machine Modbus and CAN Setting range: 0000-0011 Factory default: 0000Choose inverter as main machine or slave machine when Modbus communication. Details for Modbus, refer toAppendix 2:RS485 communication protocol.LED “0” digit: Modbus Communication Main and Slave Selection0: Slave machine Inverter is slave machine. Communication address is decided by [Fd.01]. Inverter receives orderfrom main machine and decides whether to reply or not when writing operation according to [Fd.08] setting. Reply delaytime is set by [Fd.05].1: Main machine Inverter, as main machine, sends data to communication network by broadcast orders. All slavemachines accept orders from main machine. The data sending of main machine is set by [Fd.09].LED “00” digit: CAN Communication Main and Slave Selection0: Slave machine Inverter is CAN self-defined protocol slave machine or CANopen slave machine, receiving data frommain machine on the network.1: Main machine Inverter, as main machine, sends data to communication network by broadcast orders. All slavemachines accept orders from main machine. The data sending of main machine is set by [Fd.09].Note: when inverter is regarded as the main machine setting an network, all slave machines can only beconnected to the network when using inverters of VEICHI; The main machine sends broadcast data byself-defined free protocol.Fd.01 Modbus communicationslave machine address Setting range: 1-247 Factory default: 1It sets communication address when inverter is slave machine. If inverter is main machine, this parameter has nomeaning. 0 is the broadcast address.