Annex vacon • 4924-hour support +358 (0)201 212 575 • Email: vacon@vacon.com99. ANNEXProcess Data IN (Master to Slave)Use of Process Data In variables depends on the used application. The configuration of the data isfree.Process Data OUT (Slave to Master)Use of Process Data Out variables depends on the used application.The Fieldbus Master can read the AC drive’s actual values using process data variables. Controlapplications use process data as follows:Table 50. Process Data OUT variablesNOTE 1! In Vacon 100, the Motor Current scale depends on the drive size. In Vacon 100 HVAC theMotor Current scale is always 0.1 A.NOTE 2! In Vacon 100 HVAC, the default ID is 45 meaning "Motor Current 1 Decimal". In Vacon 100,the default ID is 3 for Motor Current. The ID 45 can be mapped by the user to this variable also inVacon 100.Table 51.Register Data Default ID Information Unit2104 Process data OUT 1 1 Output Frequency 0.01 Hz2105 Process data OUT 2 2 Motor Speed 1 rpm2106 Process data OUT 3 3(45) 2 Motor Current 0.1 A2107 Process data OUT 4 4 Motor Torque 0.1 %2108 Process data OUT 5 5 Motor Power 0.1 %2109 Process data OUT 6 6 Motor Voltage 0.1 V2110 Process data OUT 7 7 DC link voltage 1 V2111 Process data OUT 8 37 Active Fault Code -