5vacon • 20 ProgrammingTel. +358 (0) 201 2121 • Fax +358 (0)201 212 2055.2 Modbus TCP parameters and monitoring values5.2.1 Ethernet common settingsTable 5. Common settings for Modbus TCP (Ethernet)5.2.2 Modbus TCP settingsTable 6. Parameters related to Modbus TCPCode Parameter Min Max Unit Default ID DescriptionP5.X.1.1 IP address mode 2482 See page 25.P5.X.1.2 IP address 2483 See page 25.P5.X.1.3 Subnet mask 2484 See page 25.P5.X.1.4 Default gateway 2485 See page 25.P5.X.1.5 MAC address 2486 See page 25.Code Parameter Min Max Unit Default ID DescriptionPARAMETERS (Common settings )P5.X.2.1.1 Connection limit 0 3 2 2446 Number of allowed con-nectionsP5.X.2.1.2 Unit identifiernumber 0 255 1 2447 See chapter 5.4.2 Mod-bus TCP settingsP5.X.2.1.3 Communicationtime-out 0 65535 s 0 2448 0 = Not usedP5.9.2.1.4.1-30 IDMap IDs 0 65535 0 IDMap IDsMONITORING VALUES (Connection 1, Monitoring *P5.X.2.2.1.1 Fieldbus protocolstatus 1 3 24491 = Stopped2 = Operational3 = FaultedP5.X.2.2.1.2 Communicationstatus 0.0 99.999 0.0 24500-99 Number of mes-sages with errors0-999 Number of mes-sages without communi-cation errorsP5.X.2.2.1.3 Illegal functions 0 2451 See page 26.P5.X.2.2.1.4 Illegal dataaddresses 0 2452 See page 26.P5.X.2.2.1.5 Illegal data values 0 2453 See page 26.P5.X.2.2.1.6 Slave device busy 0 2454 See page 26.P5.X.2.2.1.7 Memory parity error 0 2455 See page 26.P5.X.2.2.1.8 Slave device failure 0 2456 See page 27.P5.X.2.2.1.9 Last fault response 0 2457 See page 27.P5.X.2.2.1.10 Control word hex 2458 See page 33.P5.X.2.2.1.11 Status word hex 2459 See page 36.MONITORING VALUES (Connection 2, Monitoring)*