5.SETTING OF FUNCTIONS345-3. HysteresisThe Hysteresis function provides a range of high/low limit comparator off. Usually thehigh limit comparator is turned on when the indicated value is above the high limit valueand turned off when below. If you set a hysteresis range, the comparator is turned offwhen the indicated value is below the high limit value by the hysteresis setting. This iseffective in preventing chattering caused when signals are slightly varying (vibrating) .〈Comparison conditions〉・High limitON conditions :Indicated value > High limit valueOFF conditions:Indicated value ≦(High limit value - Hysteresis set value)・Low limitON conditions :Indicated value < Low limit valueOFF conditions:Indicated value ≧(Low limit value + Hysteresis set value)