UniPOS Repeater IFS7002RInstruction Manual Page 15Revision 2/16.11.09 Of 62the repeater exits Information andControl mode and on the displayappear all three panels of thescreen for Fire condition..7.4. ExampleIn a network built of 2 repeaters IFS7002R and 5 fire control panelsIFS7002 (Appendix4) have beenreported as a response detectors.In a fire condition are different zones of the plants in the "Building#2” and "Building#4".Remote panels IFS7002R, located in the objects “Security” and “Transport gate” are in Fire conditionstage I.The indication has the following:- Indicator (“Fire”) lights blinkingred light.- The local sounder produces anintermittent signal (0,5 s sound, 0,5 spause).- Text information:• Total number of fires - 3;• First registered in entrance ofBuilding#2. Phase-fire first. Time left tofire into stage II - 120 seconds• Last registered in a corridor 2nd floorof Building # 4. Phase of fire - first.Remaining time to fire stage II - 145seconds.FIRE CONDITION ZONES IN FIRE CONDITION: 3> 1 Phase 1 Zone 001 Building #2Entrance3 Phase 1 Zone 002 Building #4Korridor 2 floorTime to Phase 2: 120Time to Phase 2: 145Devices in fire condition Total number: 41 Loop 01 Zone 001 Addr 001 Object: Building #2Point 1.0012 Loop 02 Zone 003 Addr 001 Object: Building #2Point 2.0014 Loop 01 Zone 002 Addr 002 Object: Building #4Point 1.002Faults total: 00000/0000* Outputs in fault: 00000Disables total: 000 Disables outputs: 000• Suppressed message for a fire, occurred between 1 and 3 (numbers visualized fires are notconsistent, ie there is a fire with number 2, whose release is suppressed).• Total number of devices in the fire – 4.• Positions 1, 2 and 4 describe the specific device in a fire (address, outline, area, etc.).• Depressed message device in the fire, between devices with serial numbers 2 and 4 (visualizedunit numbers are not consecutive. The display can be seen the first two and last able fire alarm);The third text window: information introduced disables and faults - in this case there are no disablesand no faults.Possible actions are:- If the access level 1:• View suppressed messages for fire - buttons (“Move Up”) and (“Move Down”).• View suppressed messages for device in fire - buttons (“Move Up”) and (“Move Down”).• Add time intelligence headquarters visualized marker for selection against > - button(“Inspection”).• Suppression of local sounder - button (“Stop Alarm”).- At Access level 2, after entering a password:• All actions by the access level 1.• Force removal of connected fire control panel capable of "Fire." Reset only fire panel, visualizedmarker for selection „>” - button (“Reset Fire”) (fire in Building#2 – Entrance).The repeater remains in Fire condition until all Fire conditions in each of the fire control panelsconnected with it is reset .