E658131536 Relating communication parametersFollowing parameters should be set or changed if necessary.• Baud rate (, )... Shipment setting = : 19200bpsBaud rate of all inverters in the network (master and slave) should be same network.• Parity () ... Shipment setting = : Even parityParity of all inverters in the network (master and slave) should be same network.• Communication time-out time() ... Shipment setting = Operation is continued by the last received command value in the case of a communication break-down. To stop the operation of inverter, provide a communication time-out time (ex. = sec-ond) to the slave inverters. The master inverter does not trip even though the communication break-down happens. To trip the master inverter, provide an interlock mechanism by installing a FL faultrelay point or the like from the slave side.• Frequency point selection (, )Adjusted to the system.See chapter “6.1 Speed proportional control” for details. Setting example of parameters (2-wire RS485 communication)Parameters relating to the master side (example) Master (transmission of output frequency(%) (100% at FH)) Selection of communication protocol(Toshiba inverter protocol) Communication baud rate(ex. 19200bps) Parity (even parity) Example: Panel Example: RR/S4 input Master (sends a torque command)Parameters relating to the slave side (example) Slave (If the master inverter trips, all slave inverters stopoperating.) Selection of communication protocol(Toshiba inverter protocol) Communication time-out (ex. 1 second) Communication baud rate (same to the master side) Parity (same to the master side) Terminal block (ex. Driven by F, ST)( Run and stop of operation is controlled with the frequencyreference value by setting the “run frequency”.) Operation panel RS485 (2-wire) communication input 2-wire RS485? Adjusted to the system Point 1 setting (%) ? Ditto Point 2 frequency (Hz) ? Ditto Point 2 setting (%) ? Ditto Point 2 frequency (Hz) RS485 communication input Load sharing gain input mode selection (ex. Operationpanel input enabled) Panel load sharing gain (ex. Sharing of half of the com-mand value)