eMonitor/Alarm NotificationStrata CIX Network eMonitorStrata CTX Application Implementation Vol 3 10/07 5-17Summary MonitoringThe Strata CIX system has a buffer that stores alarms as they are generated. The contents of thealarm buffer can be automatically sent to the eMonitor as a Summary report, at 10 minute intervals,by enabling the Alarm Buffer Status parameter in the CIX.To enable sending alarm buffer data to eMonitor use eManager. Connect to the Strata CIX systemusing eManager, go to the System Alarm Control screen and enable Alarm Buffer Status (Program919, FB 02). The eMonitor must then be configured to monitor the summary alarms from that StrataCIX system.When the CIX Alarm Buffer Status is enabled and the eMonitor is configured to perform summaryalarm monitoring (per email address), summary alarms from the CIX will be sent to eMonitor every10 minutes.Important! If the eMonitor does not receive a Summary report within two cycles (approximately20 minutes) a notification alarm is sent to the configured email address. Thisnotification indicates that the CIX system or some part or the IP network connectingthe CIX system to the eMonitor is down. This notification will be sent once. Theformat of the email is as follows:When the Strata CIX system resumes sending summary alarms, eMonitor will generate anotification email as shown below:eMonitor Summary Monitoring FailureeMonitor did not receive the periodic summary alarm from the following equipment:CIX Name IP AddressLab 143 159.119.127.143eMonitor Summary MonitoringThe following equipment in back online:CIX Name IP AddressLab 143 159.119.127.143