6F2T0200 (0.15)GRE200 (1,2)- 436 -DPOS01 function (Function ID: 512001)“DPOS01_FSL_BO_CSF”(512001_8A03011DC4)DEV01_OP_INTERLOCKOperate commandwithout ILK† conditionILK† condition (“OFF”) passedPLC in DIR operateFor DIR operation512001 800301EE31Signals from user PLC logic OutputSelect logic in DPOS010.1s0 t0.6s0 t&&&Select condition‡1≥OFF-control command requiring ILK† checking(PLC#1 connection point)DEV01_OP_COMMAND512001 800301EE30OFF-control command requiring no ILK† checking(PLC#2 connection point)Operate command withILK† conditionDPOS01-OpenSelect “Failed”To BO connectionSelect “success”To “Wait for a command”For DIR operationFigure 4.1-12 Select ‘Off’ by the PLC function in DPOS01†††Note:The ILK function provides the operation criteria for “Off”.‡Note:A “select condition” signal is provided from the select condition scheme. For moreinformation, see Figure 4.1-13.††Note: To identify the input and output points of the other DPOS logics, see Table 4.1-2for the inputs (PLC#1 and PLC#2) and Table 4.1-8 for the outputs.