(3) Connecting the input signal cableStrip the sheath from the end of each conductor of a 2-core individually shielded cable as shown in Figure5.4. Twist those shields and cover them with a thermal contraction tube or vinyl tube not to make contactwith the case or core wires. Then attach an M3.5 crimping terminal with insulated sleeve as shown inFigure 5.3. Connect a crimping terminal to the A and B terminals on the terminal block and connect to eachG terminal of the detector and converter.Figure 5.3 Terminal Treatment of Flow Rate Signal CableNotes on signal cable shield processing workWhen stripping an external sheath, intermediate and insulated sheath, be careful not to scratch or cut theinternal conductors and shield mesh. Do not disjoint the shield mesh but treat it as shown in Figure 5.9.Figure 5.4 Treating the Signal Cable Shield MeshThermal contraction tube or vinyl tubeA BlackG ShieldB White25~45mmShield mesha. Open the shield mesh with a pincette or the like.b. Pull out the internal coated wires from the hole of theshielded mesh.c. Pull out all internal coated wires and extend the shield meshwire.Coated wireSeparateCrimping terminal M4: LF600F and LF610FM3.5: LF602F, LF612F, LF620F and LF622F