E6581422③5.2. RWr, RWw resistorRWr . RWw (Default value = 0)Inverter → PLC (RWr) PLC → Inverter (RWw)Address Contents Address ContentsRWr n First monitor value RWw n Monitor code (first and second)RWr n+1 Second monitor value (output frequency) RWw n+1 Set frequencyRWr n+2 Reply code RWw n+2 Instruction codeRWr n+3 Read data RWw n+3 Write data"n" is depend on the station number.5.3. Monitor codeDivide the monitor code (RWw n) into half and select the first monitor data (RWr n) from thelower 8 bits and the second monitor data (RWr n) from the higher 8 bits.(Example) When output voltage is selected for the first monitor and output torque isselected for the second monitor. -> The monitor code is 0703H.RWw n Monitor codethe higher 8 bits the lower 8 bitsSecond monitor description First monitor description* The hexadecimal value attaches and expresses "H" to the end of a number.Monitor code (When an invalid monitor code is set up, monitor value fixes to 0.)Code Number Second Monitor Description(the higher 8 bits)First Monitor Description(the lower 8 bits) Unit00H Output frequency(Second monitoronly) None monitor (Monitor value is 0) 0.01Hz01H Output frequency Output frequency 0.01Hz02H Output current Output current 0.01A03H Output voltage Output voltage 0.1V04H None monitor (Monitor value is 0) None monitor (Monitor value is 0) –05H Frequency command value Frequency command value 0.01Hz06H None monitor (Monitor value is 0) None monitor (Monitor value is 0) –07H Output torque Output torque 0.1%08H DC voltage DC voltage 0.1V09H PBR load factor PBR load factor 0.1%0AH Motor overload factor (OL2 data) Motor overload factor (OL2 data) 0.1%0BH, 0CH None monitor (Monitor value is 0) None monitor (Monitor value is 0) –0DH Input power Input power 0.01kW0EH Output power Output power 0.01kW0FH Input terminal information Input terminal information –10H Output terminal information Output terminal information –11H Output current (% monitor) Output current (% monitor) 0.1%12H Exciting current Exciting current 0.01A13H None monitor (Monitor value is 0) None monitor (Monitor value is 0) –14H Cumulative operation time Cumulative operation time 1hr15H, 16H None monitor (Monitor value is 0) None monitor (Monitor value is 0) –17H Accumulation power supply ON time Accumulation power supply ON time 1hr18H Motor overload factor Motor overload factor 0.1%19H Integral input power Integral input power 1kWh1AH Integral output power Integral output power 1kWh1BH Analog input monitor (VIA) Analog input monitor (VIA) –1CH Analog input monitor (VIB) Analog input monitor (VIB) –1DH to 20H None monitor (Monitor value is 0) None monitor (Monitor value is 0) –21H Torque current Torque current 0.1%22H, 23H None monitor (Monitor value is 0) None monitor (Monitor value is 0) –24H PID feedback value PID feedback value 0.01Hz25H to 2FH None monitor (Monitor value is 0) None monitor (Monitor value is 0) –- 18 -