E6581422③DADBDGSLDFGDADBDGSLDFGMaster unit InverterCC-Link dedicatedcableCC-Link dedicatedcableTerminationresistorDADBDGSLDFGInverterTerminationresistor110 ohm, 1/2W(130 ohm, 1/2W) 110 ohm, 1/2W(130 ohm, 1/2W)Ground(100 ohm or less)* Maximum number of units connected to one master station is 42 units (when onlyinverters are connected).* If any other units are included, the number of occupied stations depends on the unit. Sothe connectable number of units is different.4. FunctionsThis option is a communication interface unit that allows the PLC program to operate,monitor and set the parameter of the inverter as a remote station of CC-Link. It is able tocommunicate with a maximum speed of 10Mbps not only transmitting bit data but also byword data.4.1. Initial settingSet the following parameters of the inverter before begin the communication.If not change settings, cannot communicate and it becomes the cause of causing malfunction.Moreover, power supply reset is needed for confirming setting change of a parameter.List of CC-Link parameterTitle CommunicationNo. Adjustment range Default User settingf800 0800 Communication rate0: 1200bps 1: 2400bps 2: 4800bps3: 9600bps 4: 19200bps3 4( Recommended)f801 0801 Parity0: NON (No parity)1: EVEN (Even parity)2: ODD (Odd parity)1 1f803(*1)0803 Communication error trip time0: (disable)1-100s0 1 or moref805 0805 Communication waiting time0.00-2.00s0.00 –f829 0829 Selection of communication protocol0: TOSHIBA inverter protocol1: Modbus RTU protocol0 0(*2)f870 0870 Block write data 10: No selection1: Command 12: Command 23: Frequency command4: Output data on the terminal board5: Analog output for communications0 1(*2)- 13 -