Scale parameters and functions8.19 DR 30 current process valuesSIWAREX WP231Manual, 07/2014, A5E31238908A-02 115Variable Note Type Length(bytes)Rw Default Min. Max. ModbusregistersTare processweight(Page 116)Tare weight (process value) FLOAT 4 r 0 - - 3012Gross / netweight(Page 117)Gross or net weight FLOAT 4 r 0 - - 3014Gross / netweight withincreasedresolution (x10)(Page 117)Legal trade G/N weight with10x resolutionFLOAT 4 r 0 - - 3016Tare weight(Page 117)Tare FLOAT 4 r 0 - - 3018Gross processweight (com-missioningaid)(Page 117)Gross weight after dig. filter 2(process value)FLOAT 4 r 0 - - 3020Net processweight (com-missioningaid)(Page 117)Net weight after dig. filter 2(process value)FLOAT 4 r 0 - - 3022Refresh coun-ter for processvalues(Page 117)Refresh counter incrementedby 1 if weight values werechangedUSHORT 2 r 0 - - 3024Reserve 1 Reserve SHORT 2 r 0 - - 3025Last report ID(Page 117)Last generated report ID ULONG 4 r 0 - - 3026Reserve 3 Reserve FLOAT 4 r 0 - - 30288.19.2 Gross process weightThe current gross weight. Values are rounded as specified in data record DR 3 with the"Decimal places for process values" (Page 71) parameter.8.19.3 Net process weightThe current net weight. Values are rounded as specified in data record DR 3 with the"Decimal places for process values" (Page 71) parameter.8.19.4 Tare process weightThe current tare weight. Values are rounded as specified in data record DR 3 with the"Decimal places for process values" (Page 71) parameter.