5 OperatingEtherNet/IP ScannerEntry-ID: 109782314, V1.1.0, 04/2021 34© Siemens AG 2021 All rights reservedFigure 5-3: Network Settings for Adapter[1]/ S7-1200Here the settings are shown above to be:• IP: 192.168.74.45• Mask: 255.255.255.05.2.3 SIMATIC ProgramAnswering the following questions may give you a hint on what needs to becorrected.Table 5-3: LCCF_EnetScanner checksobservation possible cause remedystatus information doesn’tchange their values, whenenable is set to trueThe block is not executed place an unconditional callto the block in cyclicinterrupt programerror is true, the momentenable is set to trueParameterization error check the status code andcorrect the parameterizationvalid becomes false after acertain timeConnection problems check the status code andfollow the specificrecommendations furtherdown in the document.