Settings MenuCONFIGURATION > FUNCTION CONFIGParameter Setting Options SettingsDefault Gn1 Gn2Gn Derived E/F DisabledEnabledDisabled – –CONFIGURATION > CURRENT PROT'N > DERIVED E/F > 51N-nParameter Setting Options SettingsDefault Gn1 Gn2Gn 51N-n Element DisabledEnabledDisabled – –Gn 51N-n Setting 0.10 ⋅ Irated to 0.80 ⋅ IratedΔ 0.01 ⋅ Irated0.50 ⋅ Irated – –Gn 51N-n Char IEC-NIDTLANSI-EIANSI-VIANSI-MIIEC-LTIIEC-EIIEC-VIIEC-NI – –Gn 51N-n Time Mult(Applicable when Gn51N-n Char is IEC/ANSI)0.01 to 10.00Δ 0.011.00 – –Gn 51N-n Delay(Applicable when Gn51N-n Char is DTL)0.00s to 15.00 sΔ 0.01 s5.00 s – –Gn 51N-n MinO-perate0.00 s to 20.00 sΔ 0.01 s0.00 s – –Gn 51N-n FollowerDTL0.00 s to 20.00 sΔ 0.01 s0.00 s – –Gn 51N-n Reset IEC/ANSI Decay00 s to 60 sΔ 1 s00 s – –Gn 51N-n InrushActionOffInhibitOff – –Information ListInput/Output Matrix User Logic Type IEC 103 Modbus RTUInhibit 51N-n Inhibit 51N-n Input – –51N-n 51N-n Output Y YFunctions3.5 Time-Delayed Derived Earth Fault Protection (51N)Reyrolle, 7SR45, Device Manual 57C53000-G7040-C101-2, Edition 09.2020