159/278Siemens Building Technologies Basic Documentation LMV51... CC1P7550enHVAC Products 8 Commissioning instructions for the LMV5... system 01.10.2003The burner runs at ignition load or at the first burner stage. The positions of theactuators can now be changed.Menu level 1 Menu level 2 Menu level 3 Menu level 4 Menu level 5 Menu level 6Params & DisplayRatioControlOilSettingsCurveParamsCurve SettingsActuatorPositionsfollowednot followedIt is recommended to use the function «Actuator positions followed» to set the switchingpoints and operating points of the second and third stage.Menu level 1 Menu level 2 Menu level 3 Menu level 4 Menu level 5 Menu level 6Params & DisplayRatioControlOilSettingsCurveParamsCurve SettingsActuatorPositionsfollowednot followed————————SetPointStage1StartPointStage2OffPointStage2SetPointStage2StartPointStage3OffPointStage3SetPointStage3Stage S1 S2 on S2 off S2 S3 on S3 off S3Air 35.0° 43.0° 45.0° 53.0° 61.0° 62.0° 69.0°Aux 13.0° 28.0° 20.0° 43.0° 50.0° 50.0° 54.0°8045Fuel / air ratio contol (multistage operation)Position [°]7550d27E/050270605040302010070 100 %Air actuator position «Down»Auxiliary actuator «Down»Air actuator position «Up»Auxiliary actuator «Up»V1 V2 off V2 on V2 V3 off V3 on V3Load [%]25. Setting the burnerstagesExample: