Parameterdarstellung auf Basis der Menüstruktur AZL - Ebene «OEM» - Auslieferstand Siemens Landis&StaefaMenu level 1 Menu level 2 Menu level 3 Menu level 4 Menu level 5 Menu level 6 Description Value range AccessrightsDefaultparametersettingLMV51 LMV52132/278Siemens Building Technologies Basic Documentation LMV51... CC1P7550enHVAC Products 7 Display and operating unit AZL5... 01.10.2003Times Service x xOperatRampMod Duration operating ramp ratio control modulating operation 30..120s Service 30s x xOperatRampStageDuration operating ramp ratio control multistage operation 10..60s Service 10s x xTimeNoFlame Duration ramp in prepurge and ignition position 10..120s Service 10s x xNumFuelActuatorsNumber of fuel actuators 1..2 OEM 2 x xShutdownBehav This parameter determines the way the ratio control systembehaves in the lockout phaseUnchangedPostpurgePHomePosService HomePos x xProgramStop Program stop deactivated24 PrePurgP32 PreP FGR36 IgnitPos44 Interv 152 Interv 272 PostPPos76 PostPFGRService deactivated x xO2Ctrl/Limiter Parameter settings for O2 control and monitor function User xGasSettings Parameter settings for firing on gas Service xOptgMode Operating mode of O2 controller / monitor when firing on gas auto deactman deactO2 LimiterO2 ControlconAutoDeacService man deact xO2 Control Service xO2 Limiter Service xControl Param Service xP Low-Fire P-part of O2 controller with low-fire 3..500 % Service invalid xI Low-Fire I-part of O2 controller with low-fire 0..500s Service invalid xTau Low-Fire Time constant Tau of O2 controller's controlled system withlow-fire1..27s OEM invalid xP High-Fire P-part of O2 controller with high-fire 3..500 % Service invalid x