9. Problem ConfirmationType Code Description Measuresreversion to the normal state.E006 BATTCONNECTIONWARNINGWhen the battery connection is abnormal.This is the connection warning message,with no special change in the sequence.The warning message disappears onreversion to the normal state.[Table 9-1: Inverter general events warning list]9.1.2 INVERTER General Events (Protection)Type Code Description MeasuresPROTECTION E101 GRID RMS OVERCURRENTPROTECTIONThe product stops the generating processbecause a significant PROTECTION eventhas occurred.Wait until the event message disappears.After the event message is removed, itautomatically returns to normal.If it is not removed until the time limit isreached, it is converted to a significantevent.E102 DC LINK OVERVOLTAGEPROTECTIONThe product stops the generating processbecause a significant PROTECTION eventhas occurred.Wait until the event message disappears.After the event message is removed, itautomatically returns to normal.If it is not removed until the time limit isreached, it is converted to a significantevent.E103 PV STRING1REVERSECONNECTIONPROTECTIONThe product stops the generating processbecause a significant PROTECTION eventhas occurred.Wait until the event message disappears.After the event message is removed, itautomatically returns to normal.If it is not removed until the time limit isreached, it is converted to a significantevent.E104 PV STRING2REVERSECONNECTIONPROTECTIONThe product stops the generating processbecause a significant PROTECTION eventhas occurred.Wait until the event message disappears.After the event message is removed, itautomatically returns to normal.If it is not removed until the time limit isreached, it is converted to a significant70 Australia (Eng.) 05/2015. Rev1.1