Regency GF950L Gas Fireplace25installationCLEARANCESRef. ItemMinimum clearances (mm)NaturalDraughtFanAssisteda Below eaves, balconies and other projections:Appliances up to 50 MJ/h input 300 200Appliances up to 50 MJ/h input 500 300b From the ground, above a balcony or other surface* 300 300c From a return wall or external corner* 500 300d From a gas meter (M) (see Note 5)(see Clause 5.11, 5.9 for vent terminal location of regulator)(see Table 6.7 for New Zealand requirements)1000 1000e From an electricity meter or fuse box (P)† (see Note 5) 500 500f From a drain or soil pipe 150 75g Horizontally from any building structure* or obstruction facing a terminal 500 500h From any other flue terminal, cowl, or combustion air intake 500 300j Horizontally from an openable window, door, non-mechanical air inlet, or any other opening into a building iwththe exception of sub-floor ventilation:Appliances up to 150MJ/h input* 500 300Appliances over 150MJ/h input up to 200 MJ/h input* 1500 300Appliances over 200MJ/h inputup to 250 MJ/h input** 1500 500Appliances over 250MJ/h input* 1500 1500All fan-assisted flue appliances, in the direction of discharge - 1500k From a mechanical air inlet, including a spa blower 1500 1000n Vertically below an openable window, non-mechanical air inlet, or any other opening into a building iwth theexception of sub-floor ventilation:Space heaters up to 50MJ/h input 150 150Other appliances up to 50 MJ/h input 500 500Appliance over 50 MJ/h input and up to 150 MJ/h input 1000 1000Appliances over 150 MJ/h input 1500 1500* Unless appliance is certified for closer installation.† Prohibited area below electricity meter or fuse box extends to ground level.NOTES:1 Where dimension c, j or k cannot be achieved an equivalent horizontal distance measured diagonally from thenearest discharge point of the terminal to the opening may be deemed by the Technical Regulator to comply.2 See Clause 6. 9. 4 for restriction on the flue terminal under a covered area.3 See Figure J3 for clearances required from a flue terminal to an LP Gas cylinder. A flue terminal is consideredto be a source of ignition.4 For appliance not addressed above acceptance should be otained from the Technical Regulator.5 Minimum clearance d and e also apply to any combustion air intake openings of appliances.