3-6. Wiring type and length3 WiringWiring run Wire diameter Max. lengthControl box <--> Lobby station 0.65 mm (22 AWG) approx. 100 m1.2 mm (17 AWG) approx. 200 mControl box <--> Distribution modethe farthest distribution box0.65 mm (22 AWG) approx. 100 m1.2 mm (17 AWG) approx. 200 mControl box <-->Repeater modethe distribution box that isoperatingas a repeater0.65 mm (22 AWG) approx. 100 m1.2 mm (17 AWG) approx. 200 mRepeater modethe distribution boxthat is operatingas a repeater<--> Distribution modethe farthest distribution box0.65 mm (22 AWG) approx. 100 m1.2 mm (17 AWG) approx. 200 mDistribution box <--> Main monitor 0.65 mm (22 AWG) approx. 100 m1.2 mm (17 AWG) approx. 200 mControl box <--> The farthest lift controller 0.65 mm (22 AWG) approx. 100 m1.2 mm (17 AWG) approx. 200 mPower supply unit <-->Lobby stationControl boxDistribution boxLift controller0.65 mm (22 AWG) approx. 10 m2 mm (12 AWG) approx. 20 mPower supply unit <--> AC power source 1.2 mm (17 AWG) No requirement2 mm (12 AWG)Lobby station <--> Electric lock 0.5 mm (24 AWG) According to specification ofconnected device.1.2 mm (17 AWG)- Use 2-conductor (solid copper) wiring with a PE (polyethylene)-insulated PVC jacket.Mid-capacitance, non-shielded cable is recommended.- A certified power supply wiring has to be used with this equipment. The relevant national installation and/orequipment regulations shall be considered. A certified power supply wiring not lighter than ordinary polyvinylchloride flexible wiring according to IEC 60227 shall be used.- When connecting an electric lock to the electric lock connection terminal (K-OUT), select a device that meets the followingguidelines.– N/C or N/O dry closure contact– 12 V AC/DC, less than 1 A 32