EBL512 G3 V. 3.0.X - FIRE ALARM SOLUTIONS OPERATING INSTRUCTIONS4218.1.3. HEAVY SMOKE ALARM / HEAVY HEAT ALARMAn analog detector can activate a heavy smoke / heat alarm for a higher alarm level than the normal fire alarm level, i.e. a normalfire alarm is already activated by a detector activating a heavy smoke / heat alarm. See EBL512 G3 Planning Instructions for thesystem.Heavy smoke / heat alarm is to confirm heavy or increasing smoke / heat and can be used for special actions, e.g. activation ofsmoke ventilation, and so on.THE FOLLOWING HAPPENS IN CASE OF A HEAVY SMOKE / HEAT ALARM:• Outputs programmed for heavy smoke / heat alarm are activated. General heavy smoke / heat alarm and individual alarmpoints / zones.• Each heavy smoke / heat alarm is presented with a "title", which means "Heavy smoke" or "Heavy heat" will be added to thenormal fire alarm information:** Heavy Smoke **Zone 002 Address 03SMOKEYYYY-MM-DD hh:mmUser definable alarm text(if programmed)Menu002-03SMOKEZone AddressUser definable alarm text for 002-03Heavy smoke1 zone in alarmAlarm number 1 (of 1)Fire alarm: 002-03The printer (if available) will print each heavy smoke / heat alarm, and so on:Heavy smoke / heat alarm will be reset when the fire alarm respectively is reset,see section 19. ALARM RESET on page 50.