ANTENNAMOUNT(2 PLACES)ANTENNA(2)SCREW(2)BLACKMOUNTINGCLIPREDMOUNTINGCLIPWHITEMOUNTINGCLIPGROUNDINGLUG(2)NOTEA COMBINATION OF THESE MOUNTING CLIPS HAS BEENINCLUDED IN YOUR INSTALLATION KIT.USE THE APPROPRIATE CLIPS FOR MOUNTING.IF NO RF RECEIVER IS USED, MOUNT THE PC BOARD USINGEITHER THE WHITE OR BLACK CLIPS, WHICHEVER AREINCLUDED IN THE CONTROL PANEL'S HARDWARE KIT.DETAIL ASIDE VIEWOF BOARD -SUPPORTING SLOTSCIRCUITBOARDCABINETMOUNTINGCLIPCABINETMOUNTINGCLIPCONTROLCIRCUITBOARDBOARDSUPPORTINGSLOTSRECEIVER CIRCUIT BOARD++A Bpc_mount-001-V1DETAIL BANTENNA AND GROUNDINGLUG INSTALLATIONINSTALLATION WITH RECEIVER CIRCUIT BOARDFigure 3. Mounting the PC Board and RF ReceiverAuxiliary Device Current Draw WorksheetDEVICE CURRENT No. UNITS TOTAL CURRENT6150 Fixed-Word Keypad 40mA/70mA**6160 Alpha Keypad 40mA/150mA**6150V Fixed-Word Display Voice Keypad 60mA/160mA**6160V Alpha Display Voice Keypad 60mA/190mA**8132/8142 Series AUI (Symphony) 150mA/400mA**6270 Touch Screen Keypad 180mA/280mA**5881/5882 RF Receiver 60mA5883 Transceiver 80mA4219 Zone Expander 30mA4204 Relay Unit 15/180mA‡4229 Zone Expander/Relay Unit 30/100mA‡4286 Phone Module 300mA*(Current available from Aux. terminals = 600 mA max.)† TOTAL =*If using hardwire devices such as PIRs, refer to the specifications for that particular unit's current draw.** Values are for standby/alarm; alarm for keypads means armed with backlighting on and sounder on†In UL installations, maximum current draw from the Auxiliary Output and the Alarm Output combined must not exceed 600 mA (500 mA max from Aux. Output).‡Values are for relays OFF/relays ON.CALIFORNIA STATE FIRE MARSHALL (CSFM) AND UL RESIDENTIAL FIRE24-HOUR BATTERY BACKUP REQUIREMENTSThe California State Fire Marshal and UL have regulations which require that all residential fire alarm control panels must beprovided with a backup battery which has sufficient capacity to operate the panel and its attached peripheral devices for 24 hours in theintended standby condition, followed by at least 4 minutes in the intended fire alarm signaling condition. This control panel can meetthese requirements without using a supplementary power supply, provided that the panel’s auxiliary power and bell output currentsare limited as indicated below.OUTPUT LIMITATIONS AND CORRESPONDING REQUIRED BATTERIESOUTPUT CURRENT LIMITATIONS BATTERY INFORMATIONOutput Current Total Maximum Auxiliary Current Battery CapacityTo Use (Amp/Hrs)Recommended Battery(Yuasa Model No.)600mA maximum total ofauxiliary power plus belloutput currents45mA160mA200mA425mA500mA4AH7AH8AH14AH17.2AHNP4-12 (or ADEMCO 467)NP7-12NP4-12 (two) ‡NP7-12 (two) ‡NPG18-12‡ NOTE: Use two batteries, connected in parallel. Obtain an Ademco Battery Harness Kit SA5140-1. (Both batteries will fit inside the cabinet.)Installation and Setup Guide2-2