– 54 –Using #77 Instant Activation ModeThe #77 Instant Activation Mode is used to activate outputs, bypass zones,etc. immediately upon exiting the #77 Mode. The actions that may beactivated are relay commands, arm/disarm commands, zone bypassingcommands, and open/close access conditions.Relay CommandsAction Code Action Specifier01 Relay On Relay #02 Relay Off Relay #03 Relay Close for 2 seconds Relay #04 Relay Close XX minutes ✳ Relay #05 Relay Close YY seconds ✳ Relay #06 Relay Group On Relay Group #07 Relay Group Off Relay Group #08 Relay Group Close for 2 seconds Relay Group #09 Relay Group Close XX minutes ✳ Relay Group #10 Relay Group Close YY seconds ✳ Relay Group #✳ Check with your installer for the amount of time.Arm/Disarm CommandsActivation times 1 (Beginning), 2 (End), 3 (During) are the only valid choicesfor automatic arming and disarming functions."During" can be used to arm or disarm the control for a specific time only.For example, if "during" is selected with Arm-STAY, the system willautomatically Arm-STAY at the beginning of the window and automaticallydisarm at the end of the window.Action Code Action Specifier20 Arm-STAY Partition(s)21 Arm AWAY Partition(s)22 Disarm Partition(s)23 Force Arm STAY (Auto-bypass faulted zns) Partition(s)24 Force Arm AWAY (Auto-bypass faulted zns) Partition(s)25 Arm INSTANT Partition(s)26 Arm MAXIMUM Partition(s)